Geothermal Heat PumpsClosed Loop Water-to-Water

Hydron Module HWS060 Geothermal Heat Pump Manual

Setup, everyday use, maintenance and troubleshooting for the closed-loop water-to-water geothermal heat pump, with verified specifications.

  • ConfigurationClosed Loop Water-to-Water
  • Heating COP3.1
  • Cooling EER16.1
  • Heat cost per million Btu$16.07

About the Hydron Module HWS060

The Hydron Module HWS060 is a closed-loop water-to-water geothermal heat pump from the WS Series line. This page covers its ENERGY STAR certified closed-loop (ground-loop) rating.

In this configuration it is rated at a heating COP of 3.1 and a cooling EER of 16.1. A COP of 3.1 means it delivers about 3.1 units of heat for every unit of electricity it uses. An EER of 16.1 means it removes 16.1 Btu of heat per watt-hour in cooling. Closed-loop ratings are measured with 77 °F (25 °C) fluid entering the heat pump in cooling and 32 °F (0 °C) in heating, simulating a buried loop near the end of each season.

As a water-to-water unit it heats (and, where the system is designed for it, chills) water for radiant floors, fan coils, low-temperature radiators or a buffer tank rather than blowing air directly.

It is also recognized as ENERGY STAR Most Efficient, the program's designation for the top-performing certified products in a category.

Specifications

Hydron Module HWS060 specifications
BrandHydron Module
Model numberHWS060
Model name / seriesWS Series
ConfigurationClosed Loop Water-to-Water
Product seriesWS Series
EER (cooling efficiency)16.1 Btu/Wh
COP (heating efficiency)3.1
RefrigerantR-410A
ENERGY STAR Most EfficientYes

Certified ratings by application

1 certified rating configuration is listed for the Hydron Module HWS060, sorted by COP. Ratings depend on the application, so compare the row that matches your installation.

Certified ratings by application — Hydron Module HWS060
ApplicationEERCOPCertified
Closed Loop Water-to-Water16.13.1November 2023

Safety information

  • Installation, refrigerant work and electrical connections must be done by a licensed HVAC contractor experienced with geothermal systems, following the manufacturer's instructions and local codes. Most jurisdictions require permits for the heat pump and for drilling or trenching.
  • Geothermal heat pumps typically run on a 208/230 V circuit. Switch off the disconnect and the breaker before opening any access panel; capacitors can hold a dangerous charge after power is removed.
  • Call 811 (or your local utility-locate service) before any digging so buried gas, electric and water lines are marked.
  • Do not operate the unit with access panels or the blower door removed.
  • Closed loops are filled with water and antifreeze. Some antifreeze types (such as methanol or ethanol blends) are toxic or flammable; handle loop fluid only as directed by the installer and never drain it onto the ground or into a storm sewer.
  • If your home also has a fuel-burning furnace, boiler or water heater, keep carbon monoxide alarms on every level and near sleeping areas.

Installation and first-time setup

A geothermal system is only as good as its ground connection. The ratings for the Hydron Module HWS060 assume correct source-side flow and temperatures, so the loop or well design deserves as much attention as the heat pump itself.

  1. Room-by-room load calculation

    Insist on an ACCA Manual J heat-loss and heat-gain calculation. Geothermal equipment and loops are expensive to oversize, and an undersized loop drives entering-water temperatures down in winter, reducing capacity and efficiency.

  2. Ground-loop design

    The loop length depends on the heating and cooling loads, soil or rock thermal properties and the loop layout (vertical boreholes, horizontal trenches or a pond loop). Ask for the loop-design calculation, and for large vertical fields consider a thermal conductivity test. Reputable installers follow IGSHPA design and installation standards.

  3. Flush, purge and pressure-test

    The loop must be flushed at high velocity to remove air and debris, pressure-tested, and filled with the antifreeze concentration your climate requires. Ask for the freeze-protection temperature in writing.

  4. Hydronic distribution

    Design the heating side for the lowest practical supply-water temperature — radiant floors and oversized low-temperature emitters let the heat pump run far more efficiently than high-temperature baseboard. Most installations use a buffer tank to prevent short-cycling, plus an expansion tank, air separator and mixing or limit controls where required.

  5. Verify water flow

    Source-side flow must match the manufacturer's table — closed loops commonly run about 2.5–3 gpm per ton, while open loops often use less. Ask the installer to record flow and the temperature difference across the heat exchanger.

  6. Commissioning

    Ask for a start-up report that records entering and leaving source temperatures, refrigerant pressures, airflow or load-side flow, thermostat and auxiliary-heat settings, and the loop fluid freeze point where applicable.

Using your geothermal heat pump

Thermostat settings

Choose a comfortable setpoint and leave it. Geothermal heat pumps work best holding a steady temperature; large setbacks in heating mode can bring on auxiliary electric heat during recovery, which costs several times more per hour than the compressor. If you use setbacks, keep them to a few degrees or use a thermostat with heat-pump adaptive recovery.

Auxiliary and emergency heat

Hydronic geothermal systems are often paired with a backup boiler or an electric element in the buffer tank. The controls should call for backup heat only when the heat pump cannot keep up; if the backup runs often in mild weather, ask your installer to review the staging settings.

Supply-water temperature

Efficiency falls as the heating supply temperature rises. Use the lowest setting (or the outdoor-reset curve) that keeps the house comfortable, and avoid raising the setpoint to "speed up" warm-up — radiant systems respond slowly by design.

If the system also provides chilled water for cooling, the controls must keep surface and pipe temperatures above the indoor dew point to prevent condensation on radiant floors and uninsulated piping.

Domestic hot water

Many geothermal units can be fitted with a desuperheater that preheats domestic hot water using waste heat from the compressor. If your installation has one, its circulator runs only when the compressor runs, and the water heater still provides final heating — check with your installer whether it was included.

Care and maintenance

Ground loops have no outdoor coil to clean and are largely maintenance-free, but the indoor unit and the source-side fluid still need periodic attention.

WhenWhat to do
Every 3 monthsCheck system pressure on the hydronic side and listen for air in the piping; bleed air as the installer showed you.
Every seasonCheck that the condensate drain and trap are clear (water-to-air units remove moisture in cooling mode) and that nothing is stored against the unit's access panels.
Every yearProfessional service: check loop pressure and flow, verify antifreeze concentration and freeze protection, record entering and leaving water temperatures, and inspect electrical connections and the compressor.
Every yearCheck the expansion tank pre-charge, buffer-tank temperatures, circulator operation and any mixing valves on the load side.
Every 3–5 yearsHave the indoor coil and blower (or load-side heat exchanger) inspected and cleaned if airflow or temperature split has dropped.

Troubleshooting

Geothermal heat pumps protect themselves with pressure and temperature switches, so most "no heat" calls trace back to airflow, water flow or thermostat settings. Work through the checks below before calling a technician.

ProblemPossible causeWhat to try
No heating or coolingThermostat in wrong mode; tripped breaker; disconnect off; unit in safety lockout.Check mode and setpoint; reset the breaker once. Many units clear a lockout when power is cycled off and on — if it locks out again, call for service.
Unit locks out in heating modeLow source-side flow; entering water too cold; low antifreeze concentration; dirty air filter.Replace the filter and confirm loop or well pumps run. Repeated low-temperature lockouts point to a flow, antifreeze or loop-sizing problem for a technician.
Unit locks out in cooling modeHigh head pressure from low water flow, a scaled heat exchanger or poor airflow.Check the filter and blower; have a technician verify flow and the temperature rise across the heat exchanger.
High electric bills in winterAuxiliary heat running too often; deep thermostat setbacks; loop delivering cold water.Reduce setbacks and ask your contractor to review auxiliary-heat staging and entering-water temperatures.
Air from vents feels lukewarmNormal heat-pump supply temperature (around 90–105 °F).Judge comfort by whether the house reaches setpoint, not by the feel of the air.
Gurgling or rushing water soundsAir trapped in the loop or hydronic piping.A technician should purge the air; persistent air may mean a slow leak.
Water near the unitClogged condensate drain or trap; leaking fitting.Turn the unit off, clear the drain and check fittings; call for service if water continues.
Some zones not heatingAir in the zone; zone valve or circulator not opening; supply temperature set too low.Bleed air, check the zone thermostat, and have the controls and circulators tested.

Energy use and running costs

At its rated COP of 3.1, the Hydron Module HWS060 uses about 95 kWh of electricity per million Btu of heat delivered — roughly $16.07 at $0.17 per kWh.

Example: a home that needs 50 million Btu of delivered heat per year (roughly a mid-size house in a cold northern climate). Electricity at $0.17 per kWh; natural gas at $1.50 per therm.
Heat sourceEnergy usedEstimated cost
This heat pump (COP 3.1)4,727 kWh$804
Electric resistance heat (COP 1.0)14,654 kWh$2,491
95% AFUE gas furnace526 therms$789
80% AFUE gas furnace625 therms$938

For cooling, an EER of 16.1 means each ton of capacity (12,000 Btu/h) draws about 0.75 kW at the rating point. Over 1,000 full-load cooling hours a year — an assumption typical of a mixed U.S. climate — that is about 745 kWh per ton, or $127 per ton at $0.17 per kWh. Multiply by your system's tonnage for a seasonal estimate.

These figures are based on the certified rating point. Real-world performance changes with loop temperatures through the season, and the published ratings include only a small allowance for pumping — the full energy of the loop circulator is extra. A well-designed loop with efficient circulators keeps that penalty small.

Frequently asked questions

What are the efficiency ratings of the Hydron Module HWS060?

In its closed-loop water-to-water configuration it is rated at an EER of 16.1 for cooling and a COP of 3.1 for heating. Closed-loop ratings use 77 °F entering fluid for cooling and 32 °F for heating.

Can the Hydron Module HWS060 be used with both open and closed loops?

This listing covers its closed-loop rating. Manufacturers often certify the same water-source unit separately for closed-loop and open-loop use, each with its own EER and COP, so check the Hydron Module literature (or other listings for model HWS060) for the configuration you plan to install.

How much does it cost to heat with the Hydron Module HWS060?

At a COP of 3.1 it needs about 95 kWh per million Btu of heat, or about $16.07 at $0.17/kWh. A home needing 50 million Btu a year would spend roughly $804, before loop-pump energy and any auxiliary heat.

What refrigerant does the Hydron Module HWS060 use?

The ENERGY STAR record lists R-410A.

Does the Hydron Module HWS060 heat with forced air or hot water?

Hot water. It is a closed-loop water-to-water unit that heats water for radiant floors, fan coils, low-temperature radiators or a buffer tank; it does not blow air on its own.

Is the Hydron Module HWS060 ENERGY STAR certified?

Yes. It appears on the ENERGY STAR certified geothermal heat pump list, with a certification date of November 2023, and it is also designated ENERGY STAR Most Efficient.

Sources and disclaimer

Specifications on this page come from the ENERGY STAR certified geothermal heat pumps dataset published by the U.S. Environmental Protection Agency (record certified November 29, 2023), retrieved October 7, 2026.

The setup, operating, maintenance and troubleshooting guidance is written by ManualHarbor's editors for this specific product type and configuration. It is an independent guide — not a reproduction of the manufacturer's manual — and ManualHarbor is not affiliated with Hydron Module. Always follow the safety instructions, installation requirements and warranty terms supplied with your unit, and contact Hydron Module or an authorized service provider for warranty repairs and replacement parts.

Running-cost figures use assumed U.S. average utility prices and are estimates for comparison only. See our editorial methodology for details.