Geothermal Heat PumpsOpen Loop Water-to-Air

Keeprite HB036V******1**1 Geothermal Heat Pump Manual

Setup, everyday use, maintenance and troubleshooting for the open-loop water-to-air geothermal heat pump, with verified specifications.

  • ConfigurationOpen Loop Water-to-Air
  • Heating COP4.9
  • Cooling EER25.9
  • Heat cost per million Btu$10.17

About the Keeprite HB036V******1**1

Keeprite model HB036V******1**1 from the HB line is listed by ENERGY STAR as an open-loop water-to-air geothermal heat pump.

In this configuration it is rated at a heating COP of 4.9 and a cooling EER of 25.9. A COP of 4.9 means it delivers about 4.9 units of heat for every unit of electricity it uses. An EER of 25.9 means it removes 25.9 Btu of heat per watt-hour in cooling. Open-loop ratings are measured with 59 °F (15 °C) water entering the heat pump in cooling and 50 °F (10 °C) in heating, simulating well water. That warmer winter source is why open-loop figures run higher than closed-loop figures for the same hardware.

As a water-to-air unit it heats and cools through ductwork like a conventional furnace and air conditioner, with the outdoor condenser replaced by the ground loop. Among peers, its COP is higher than 75% of the 1,510 Open Loop Water-to-Air models in our database and its EER beats 63% of them.

It is also recognized as ENERGY STAR Most Efficient, the program's designation for the top-performing certified products in a category.

Specifications

Keeprite HB036V******1**1 specifications
BrandKeeprite
Model numberHB036V******1**1
Model name / seriesHB
ConfigurationOpen Loop Water-to-Air
Product seriesHB
EER (cooling efficiency)25.9 Btu/Wh
COP (heating efficiency)4.9
RefrigerantR-410A
ENERGY STAR Most EfficientYes

Certified ratings by application

2 certified rating configurations are listed for the Keeprite HB036V******1**1, sorted by COP. Ratings depend on the application, so compare the row that matches your installation.

Certified ratings by application — Keeprite HB036V******1**1
ApplicationEERCOPCertified
Open Loop Water-to-Air25.94.9December 2024
Closed Loop Water-to-Air19.73.9December 2024

Safety information

  • Installation, refrigerant work and electrical connections must be done by a licensed HVAC contractor experienced with geothermal systems, following the manufacturer's instructions and local codes. Most jurisdictions require permits for the heat pump and for drilling or trenching.
  • Geothermal heat pumps typically run on a 208/230 V circuit. Switch off the disconnect and the breaker before opening any access panel; capacitors can hold a dangerous charge after power is removed.
  • Call 811 (or your local utility-locate service) before any digging so buried gas, electric and water lines are marked.
  • Do not operate the unit with access panels or the blower door removed.
  • Open-loop systems draw from and return water to an aquifer or surface water. Wells and discharge methods are regulated in most states — use a licensed well driller and follow local discharge and permitting rules.
  • If your home also has a fuel-burning furnace, boiler or water heater, keep carbon monoxide alarms on every level and near sleeping areas.

Installation and first-time setup

A geothermal system is only as good as its ground connection. The ratings for the Keeprite HB036V******1**1 assume correct source-side flow and temperatures, so the loop or well design deserves as much attention as the heat pump itself.

  1. Room-by-room load calculation

    Insist on an ACCA Manual J heat-loss and heat-gain calculation. Geothermal equipment and loops are expensive to oversize, and an undersized loop drives entering-water temperatures down in winter, reducing capacity and efficiency.

  2. Well yield and water quality

    An open loop needs a reliable well with enough yield for the heat pump at full load, plus a legal way to return the water (a return well or approved surface discharge). Test the water for iron, hardness, pH and sediment — poor water quality fouls the heat exchanger and may call for a cupronickel coil or a closed loop instead.

  3. Pump and flow control

    The well pump should be sized for the heat pump's required flow, and a flow-control or solenoid valve should stop water flow whenever the compressor is off so you are not pumping water for nothing.

  4. Ductwork and airflow

    Have the contractor measure external static pressure and set blower airflow to the manufacturer's table (commonly 350–450 CFM per ton). Leaky or undersized ducts are the most common reason a new system underperforms.

  5. Verify water flow

    Source-side flow must match the manufacturer's table — closed loops commonly run about 2.5–3 gpm per ton, while open loops often use less. Ask the installer to record flow and the temperature difference across the heat exchanger.

  6. Commissioning

    Ask for a start-up report that records entering and leaving source temperatures, refrigerant pressures, airflow or load-side flow, thermostat and auxiliary-heat settings, and the loop fluid freeze point where applicable.

Using your geothermal heat pump

Thermostat settings

Choose a comfortable setpoint and leave it. Geothermal heat pumps work best holding a steady temperature; large setbacks in heating mode can bring on auxiliary electric heat during recovery, which costs several times more per hour than the compressor. If you use setbacks, keep them to a few degrees or use a thermostat with heat-pump adaptive recovery.

Auxiliary and emergency heat

Many water-to-air systems include electric resistance backup. "Auxiliary" heat should come on only during very cold weather or quick recovery; "emergency" heat locks out the compressor and should be used only if the heat pump fails. Frequent auxiliary heat in mild weather is worth a service call.

Cooling and humidity

Set the fan to "Auto" in summer so moisture collected on the indoor coil drains away instead of re-evaporating into the house. Supply air in heating mode is often around 90–105 °F — cooler than a gas furnace — so the air from the registers may feel mild even though the house is being heated properly.

Domestic hot water

Many geothermal units can be fitted with a desuperheater that preheats domestic hot water using waste heat from the compressor. If your installation has one, its circulator runs only when the compressor runs, and the water heater still provides final heating — check with your installer whether it was included.

Care and maintenance

Ground loops have no outdoor coil to clean and are largely maintenance-free, but the indoor unit and the source-side fluid still need periodic attention.

WhenWhat to do
Every 1–3 monthsInspect the air filter and replace it when dirty (1 in. filters usually monthly to quarterly; 4–5 in. media filters every 6–12 months).
Every seasonCheck that the condensate drain and trap are clear (water-to-air units remove moisture in cooling mode) and that nothing is stored against the unit's access panels.
Every yearProfessional service: clean any strainer, check well-pump operation and flow, and compare water temperature drop across the heat exchanger. Mineral scaling or iron fouling may call for acid cleaning of the coaxial heat exchanger.
Every 3–5 yearsHave the indoor coil and blower (or load-side heat exchanger) inspected and cleaned if airflow or temperature split has dropped.

Troubleshooting

Geothermal heat pumps protect themselves with pressure and temperature switches, so most "no heat" calls trace back to airflow, water flow or thermostat settings. Work through the checks below before calling a technician.

ProblemPossible causeWhat to try
No heating or coolingThermostat in wrong mode; tripped breaker; disconnect off; unit in safety lockout.Check mode and setpoint; reset the breaker once. Many units clear a lockout when power is cycled off and on — if it locks out again, call for service.
Unit locks out in heating modeLow source-side flow; entering water too cold; low antifreeze concentration; dirty air filter.Replace the filter and confirm loop or well pumps run. Repeated low-temperature lockouts point to a flow, antifreeze or loop-sizing problem for a technician.
Unit locks out in cooling modeHigh head pressure from low water flow, a scaled heat exchanger or poor airflow.Check the filter and blower; have a technician verify flow and the temperature rise across the heat exchanger.
High electric bills in winterAuxiliary heat running too often; deep thermostat setbacks; loop delivering cold water.Reduce setbacks and ask your contractor to review auxiliary-heat staging and entering-water temperatures.
Air from vents feels lukewarmNormal heat-pump supply temperature (around 90–105 °F).Judge comfort by whether the house reaches setpoint, not by the feel of the air.
Gurgling or rushing water soundsAir trapped in the loop or hydronic piping.A technician should purge the air; persistent air may mean a slow leak.
Water near the unitClogged condensate drain or trap; leaking fitting.Turn the unit off, clear the drain and check fittings; call for service if water continues.
Rusty or slimy deposits; falling capacityIron bacteria, iron or scale from the well water fouling the heat exchanger.Have the water tested and the heat exchanger cleaned; discuss water treatment or a closed loop if fouling recurs.

Energy use and running costs

At its rated COP of 4.9, the Keeprite HB036V******1**1 uses about 60 kWh of electricity per million Btu of heat delivered — roughly $10.17 at $0.17 per kWh.

Example: a home that needs 50 million Btu of delivered heat per year (roughly a mid-size house in a cold northern climate). Electricity at $0.17 per kWh; natural gas at $1.50 per therm.
Heat sourceEnergy usedEstimated cost
This heat pump (COP 4.9)2,991 kWh$508
Electric resistance heat (COP 1.0)14,654 kWh$2,491
95% AFUE gas furnace526 therms$789
80% AFUE gas furnace625 therms$938

For cooling, an EER of 25.9 means each ton of capacity (12,000 Btu/h) draws about 0.46 kW at the rating point. Over 1,000 full-load cooling hours a year — an assumption typical of a mixed U.S. climate — that is about 463 kWh per ton, or $78.76 per ton at $0.17 per kWh. Multiply by your system's tonnage for a seasonal estimate.

These figures are based on the certified rating point. Real-world performance changes with well-water temperature and pumping depth, and the published ratings include only a small allowance for pumping — the full energy of the well pump is extra. A correctly sized well pump that shuts off with the compressor keeps that penalty small.

Frequently asked questions

What are the efficiency ratings of the Keeprite HB036V******1**1?

In its open-loop water-to-air configuration it is rated at an EER of 25.9 for cooling and a COP of 4.9 for heating. Open-loop ratings use 59 °F entering water for cooling and 50 °F for heating.

Can the Keeprite HB036V******1**1 be used with both open and closed loops?

This listing covers its open-loop rating. Manufacturers often certify the same water-source unit separately for closed-loop and open-loop use, each with its own EER and COP, so check the Keeprite literature (or other listings for model HB036V******1**1) for the configuration you plan to install.

How much does it cost to heat with the Keeprite HB036V******1**1?

At a COP of 4.9 it needs about 60 kWh per million Btu of heat, or about $10.17 at $0.17/kWh. A home needing 50 million Btu a year would spend roughly $508, before loop-pump energy and any auxiliary heat.

What refrigerant does the Keeprite HB036V******1**1 use?

The ENERGY STAR record lists R-410A.

Does the Keeprite HB036V******1**1 heat with forced air or hot water?

Forced air. It is an open-loop water-to-air unit, so it delivers heating and cooling through ductwork with an indoor blower, like a furnace and central air conditioner.

Is the Keeprite HB036V******1**1 ENERGY STAR certified?

Yes. It appears on the ENERGY STAR certified geothermal heat pump list, with a certification date of December 2024, and it is also designated ENERGY STAR Most Efficient.

Sources and disclaimer

Specifications on this page come from the ENERGY STAR certified geothermal heat pumps dataset published by the U.S. Environmental Protection Agency (record certified December 10, 2024), retrieved October 7, 2026.

The setup, operating, maintenance and troubleshooting guidance is written by ManualHarbor's editors for this specific product type and configuration. It is an independent guide — not a reproduction of the manufacturer's manual — and ManualHarbor is not affiliated with Keeprite. Always follow the safety instructions, installation requirements and warranty terms supplied with your unit, and contact Keeprite or an authorized service provider for warranty repairs and replacement parts.

Running-cost figures use assumed U.S. average utility prices and are estimates for comparison only. See our editorial methodology for details.