Heat PumpsSplit System

GE NS16H24SA5-**A Heat Pump Manual

Setup, everyday use, maintenance and troubleshooting for the 2-ton split-system heat pump, with verified specifications.

  • Capacity2 tons
  • SEER215.2–16.0
  • HSPF27.8–8.2
  • Matched systems99

About the GE NS16H24SA5-**A

The GE NS16H24SA5-**A is a 2-ton split-system heat pump from the NS16H Series series, listed as ENERGY STAR certified in 99 AHRI-matched systems.

Depending on the indoor unit it is paired with, efficiency ranges from 15.2–16.0 SEER2 and 7.8–8.2 HSPF2. The matched indoor coil or air handler matters: always confirm the exact combination on an AHRI certificate before purchase, because rebates and efficiency claims apply only to certified matches.

It uses a single-stage compressor that runs at full capacity whenever it operates — simple and robust, but less efficient at part load than multi-stage designs.

Specifications

GE NS16H24SA5-**A specifications
BrandGE
Model numberNS16H24SA5-**A
Model name / seriesNS16H Series
System typeSplit System
Product seriesNS16H Series
Nominal cooling capacity24,000 Btu/h
SEER2 (cooling efficiency)15.2–16.0
EER2 (peak cooling efficiency)12.0–13.8
HSPF2 (heating efficiency)7.8–8.2
Heating capacity at 47 °F22,000 Btu/h
Max heating capacity at 17 °F14,700 Btu/h
Max heating capacity at 5 °F11,600 Btu/h
Best COP at 5 °F2.20
Compressor stagingSingle stage
RefrigerantR-454B (GWP:470 | Lower GWP)
ENERGY STAR cold-climate match availableNo
Connected / demand-response capableNo
AHRI-matched systems listed99
ENERGY STAR Most Efficient match availableNo

AHRI-matched systems

99 certified indoor/outdoor combinations are listed for the GE NS16H24SA5-**A, sorted by SEER2. The 25 most efficient are shown below. Each row links to a page with that system's full ratings and guidance.

AHRI-matched systems — GE NS16H24SA5-**A
AHRI ref.Indoor unitSEER2EER2HSPF2Cooling Btu/h
216497348NAM30E1TA5*-**16.013.88.124,000
216497393NCU[C,U]30BT5*-**+TDRwith furnace NF80U090S4B*15.513.28.124,000
216497397NCU[C,U]30BT5*-**+TDRwith furnace NF97U045V3B*15.513.08.024,000
216497401NCU[C,U]30BT5*-**+TDRwith furnace NF98U070M3B*15.513.08.024,000
216497404NCHC24AT5*-**+TDRwith furnace NF80U045T3A*15.513.27.823,400
216497428NCHC30AT5*-**+TDRwith furnace NF80U045T3A*15.513.27.823,400
216497360NCU[C,U]24AT5*-**+TDRwith furnace NF80U070S3A*15.513.07.823,400
216497359NCU[C,U]24AT5*-**+TDRwith furnace NF80L045S3A*15.513.27.823,200
216497361NCU[C,U]24AT5*-**+TDRwith furnace NF80L070S3A*15.513.07.823,400
216497362NCU[C,U]24AT5*-**+TDRwith furnace NF80X060V3A*15.513.07.823,600
216497445NCHC30BT5*-**+TDRwith furnace NF97U045V3B*15.513.27.823,800
216497448NCHC30BT5*-**+TDRwith furnace NF97X060V3B*15.513.27.823,800
216497351NAM30V1TA5*-**15.513.68.124,000
216497353NAM30V2TA5*-**15.513.08.224,000
216497356NCU[C,U]24AT5*-**+TDRwith furnace NF80U045T3A*15.513.27.823,400
216497392NCU[C,U]30BT5*-**+TDRwith furnace NF80L070S3B*15.513.28.024,000
216497391NCU[C,U]30BT5*-**+TDRwith furnace NF80U070S3B*15.513.28.024,000
216497373NCU[C,U]24BT5*-**+TDRwith furnace NF97U045V3B*15.513.07.823,400
216497377NCU[C,U]24BT5*-**+TDRwith furnace NF98U070M3B*15.513.07.823,600
216497380NCU[C,U]30AT5*-**+TDRwith furnace NF80U045T3A*15.513.28.024,000
216497414NCHC24BT5*-**+TDRwith furnace NF80U090T4B*15.513.28.124,000
216497415NCHC24BT5*-**+TDRwith furnace NF80U070S3B*15.513.28.123,800
216497416NCHC24BT5*-**+TDRwith furnace NF80L070S3B*15.513.28.123,800
216497417NCHC24BT5*-**+TDRwith furnace NF80U090S4B*15.513.48.124,000
216497418NCHC24BT5*-**+TDRwith furnace NF80L090S4B*15.513.48.124,000

Safety information

  • Installation, refrigerant charging and electrical connection must be performed by a licensed HVAC contractor in accordance with local codes and the manufacturer's installation instructions. Many jurisdictions require a permit and inspection.
  • Turn off power at the outdoor disconnect and at the main panel before opening any service panel. Capacitors can hold a dangerous charge after power is removed.
  • Keep children and pets away from the outdoor unit; never insert objects through the fan guard.
  • Do not operate the system with panels or the fan guard removed.
  • If a gas furnace provides backup heat, make sure carbon monoxide alarms are installed on every level of the home and near sleeping areas.

Installation and sizing

Proper installation matters more than any rating on the label: field studies show that incorrect charge, poor airflow and leaky ducts can cut real-world efficiency by 30% or more. Use the checklist below when reviewing quotes for the GE NS16H24SA5-**A.

  1. Load calculation

    Insist on a room-by-room heat-loss and heat-gain calculation (ACCA Manual J) before choosing a size. Oversized heat pumps short-cycle, dehumidify poorly and wear out sooner; rule-of-thumb sizing by square footage is unreliable.

  2. Verify the matched system

    Confirm the outdoor unit, indoor coil or air handler (and furnace, if any) match an AHRI certificate. Mismatched components can lower efficiency well below the published ratings and may void rebates.

  3. Outdoor unit placement

    Set the condenser on a level pad raised above expected snow depth, with at least 12–24 in. of clearance around the coil and 5 ft above the fan. Avoid spots under roof drip lines where ice can fall onto the unit.

  4. Ductwork and airflow

    Have the contractor measure static pressure and set blower airflow (typically 350–450 CFM per ton). Leaky or undersized ducts are the most common reason a new system underperforms.

  5. Line set and charge

    The refrigerant line set should be pressure-tested, evacuated to 500 microns or lower and charged by weight and verified by subcooling or superheat as the manufacturer specifies.

  6. Commissioning

    Ask for a commissioning report showing airflow, refrigerant charge readings, thermostat configuration (including auxiliary-heat lockout) and a test of defrost operation.

Using your heat pump

Thermostat settings

Pick a comfortable setpoint and leave it. Heat pumps are most efficient when they hold a steady temperature; deep night setbacks in heating mode can trigger expensive auxiliary (strip) heat during recovery. If you use setbacks, limit them to 2–3 °F or use a thermostat with adaptive recovery designed for heat pumps.

Heating mode and defrost

In cold, damp weather frost builds up on the outdoor coil. The unit periodically reverses into a defrost cycle for a few minutes — you may see steam rising from the outdoor unit and hear a whoosh when the reversing valve shifts. This is normal.

Heating output drops as outdoor temperature falls. Below the system's balance point a backup heat source (electric strips or a furnace) supplements the heat pump; your installer should set the thermostat so backup heat runs only when needed.

Cooling and dehumidification

For better humidity control in summer, use the "Auto" fan setting rather than "On" so moisture collected on the indoor coil can drain away instead of re-evaporating into the house.

Care and maintenance

WhenWhat to do
Every 1–3 monthsCheck the air filter and replace it when dirty (1 in. filters usually monthly to quarterly; 4–5 in. media filters every 6–12 months).
Monthly in seasonKeep 2 ft clear around the outdoor unit: remove leaves, grass clippings, snow and ice. Never cover the unit while it is in use.
Each springGently hose the outdoor coil from the inside out with power off; straighten bent fins with a fin comb.
Each fallConfirm the condensate drain is clear and the outdoor unit is level and not sinking into the ground.
Every yearSchedule professional maintenance: electrical connections, capacitor test, refrigerant charge check, coil cleaning, blower and drain service, and a defrost test.

Troubleshooting

ProblemPossible causeWhat to try
No heating or coolingThermostat in wrong mode; tripped breaker or blown fuse; outdoor disconnect off.Check mode and setpoint; reset the breaker once; confirm both indoor and outdoor disconnects are on. If it trips again, call a technician.
Steam from the outdoor unit in winterNormal defrost cycle.No action needed; defrost typically lasts 2–10 minutes.
Outdoor unit covered in iceDefrost control or sensor fault; low refrigerant; blocked airflow; gutter dripping on unit.Clear snow and debris; redirect dripping water. If the coil stays encased in ice for hours, switch to emergency heat and call for service.
Air from vents feels lukewarm in heatingHeat pumps deliver air around 90–100 °F, cooler than a furnace.Normal. Check that the house is reaching setpoint rather than judging by air temperature.
High electric bills in winterAuxiliary strip heat running too often; deep setbacks; dirty filter.Reduce setbacks; ask your contractor to set an aux-heat lockout; replace the filter.
Short cyclingOversized system; thermostat near a supply register; refrigerant or control issue.Relocate the thermostat if needed; have the contractor verify sizing and charge.
Water dripping indoorsClogged condensate drain or pump; dirty coil; frozen evaporator.Turn the system off and clear the drain line; if ice is visible on the coil, check the filter and airflow before restarting.
Unusual noises (grinding, squealing)Fan motor bearings; debris in the fan; loose panel.Turn the system off and call a technician — continued operation can damage the compressor or motor.

Energy use and running costs

Assuming 1,000 full-load cooling hours per year (typical of a moderate U.S. climate), the most efficient matched system would use roughly 1,500 kWh for cooling — about $255 at $0.17/kWh.

For heating, 1,500 full-load hours at 8.2 HSPF2 works out to about 4,024 kWh, or $684 per year, excluding any auxiliary heat. The same heat from an 80% AFUE gas furnace would cost about $619 at $1.50/therm.

Your actual cost depends on climate, home insulation, thermostat habits and local utility rates. Use these figures to compare models rather than as a bill forecast.

Frequently asked questions

What size is the GE NS16H24SA5-**A?

Its most common rated cooling capacity is 24,000 Btu/h, or about 2 tons. The exact capacity depends on the matched indoor unit.

What is the SEER2 rating of the GE NS16H24SA5-**A?

Certified matches range from 15.2–16.0 SEER2 and 7.8–8.2 HSPF2, depending on the indoor coil or air handler.

Is the GE NS16H24SA5-**A a cold-climate heat pump?

None of its listed matches meet the ENERGY STAR cold-climate criteria. It is best suited to moderate climates or homes with a backup heat source.

What refrigerant does the GE NS16H24SA5-**A use?

R-454B (GWP:470 | Lower GWP).

Which indoor units are compatible with the GE NS16H24SA5-**A?

99 certified indoor/outdoor combinations are listed. See the matched systems table on this page for each indoor model, AHRI number and rating.

Sources and disclaimer

Specifications on this page come from the ENERGY STAR certified heat pumps dataset published by the U.S. Environmental Protection Agency (record certified October 26, 2025), retrieved October 7, 2026.

The setup, operating, maintenance and troubleshooting guidance is written by ManualHarbor's editors for this specific product type and configuration. It is an independent guide — not a reproduction of the manufacturer's manual — and ManualHarbor is not affiliated with GE. Always follow the safety instructions, installation requirements and warranty terms supplied with your unit, and contact GE or an authorized service provider for warranty repairs and replacement parts.

Running-cost figures use assumed U.S. average utility prices and are estimates for comparison only. See our editorial methodology for details.