UPS Battery BackupsMulti-Mode Double-Conversion

Liebert ITA2-15KRT208C UPS Battery Backup Manual

Setup, everyday use, maintenance and troubleshooting for the 15 kVA / 15 kW multi-mode double-conversion UPS, with verified specifications.

  • Rating15 kVA / 15 kW
  • TopologyMulti-Mode Double-Conversion
  • Efficiency94.5%
  • Runtime at half load23 min

About the Liebert ITA2-15KRT208C

The Liebert ITA2-15KRT208C is a 15 kVA / 15 kW multi-mode double-conversion UPS certified under the ENERGY STAR program for uninterruptible power supplies. It is marketed as the Liebert ITA2 15KVA.

It can support up to 15 kW of connected equipment (15 kVA apparent power, a 1.00 output power factor). It is rated for 208–220 V, 50/60 Hz input. Energy storage is a valve-regulated lead-acid (VRLA) battery (internal), with a 1-year warranty listed in the certification record.

ENERGY STAR weighted efficiency is 94.5%, and 94% at half load. With nothing connected it draws 151 W. Its weighted efficiency is higher than 41% of the 348 Multi-Mode Double-Conversion models in our database.

The manufacturer lists it for consumer, commercial, and data center applications.

Specifications

Liebert ITA2-15KRT208C specifications
BrandLiebert
Model numberITA2-15KRT208C
Model name / seriesLiebert ITA2 15KVA
TopologyMulti-Mode Double-Conversion
Apparent power rating15,000 VA
Real power rating15,000 W
Output power factor (W/VA)1.00
Default normal modeVFD (voltage and frequency dependent)
Multiple normal modesYes
Intended applicationsConsumer, Commercial, Data Center
Rated input voltage208–220 V
Rated output voltage208–220 V
Input frequency50/60 Hz
Battery technologyValve-regulated lead-acid (VRLA)
Battery locationInternal
Runtime at full load8 min
Runtime at half load23 min
Battery warranty1 years
Weighted efficiency (ENERGY STAR)94.5%
Efficiency at 25% load92.9%
Efficiency at 50% load94.0%
Efficiency at 75% load93.9%
Efficiency at 100% load93.4%
Input power at no load151.3 W
Input power factor0.99
Rack-mountableNo
Height5.1 in.
Width16.9 in.
Depth23.2 in.
Modular designYes
Communication portsUSB
Manufacturer take-back programNo

Safety information

  • Units of this size may require a dedicated circuit, a locking plug or hardwired connection. Have a licensed electrician verify the circuit and receptacle for the 208–220 V input rating before installation.
  • The UPS contains a battery that can deliver dangerous energy even when the unit is unplugged, and its outlets may be live on battery power. Do not open the enclosure except to replace batteries as described in the manual.
  • Install the UPS indoors in a clean, dry, well-ventilated location away from heat sources and direct sunlight. High temperatures shorten battery life sharply.
  • Battery-equipped UPS units are heavy. Use at least two people (or a lift) to move or rack-mount the unit.

Installation and first-time setup

Size the load first. Add up the wattage of the equipment you plan to protect (check each power supply label or measure it with a plug-in meter). Keep the total below the 15 kW rating — ideally under about 12 kW (80%) to leave headroom for start-up surges and battery aging. The 15 kVA figure is apparent power; the watt rating is the one that limits most modern IT equipment.

  1. Inspect and position

    Unpack the UPS and check for shipping damage. Place it on a hard, level surface with the ventilation openings unobstructed.

  2. Connect the battery

    Many UPS units ship with the battery disconnected for safety. If so, connect it as shown in the quick-start guide before plugging in.

  3. Connect input power

    Connect the UPS to its dedicated circuit (208–220 V) as specified in the installation manual.

  4. Charge the battery

    Turn the UPS on and let it charge for several hours before relying on full runtime. Equipment can be connected and used during charging, but runtime will be limited until the battery is full.

  5. Connect equipment

    Connect the critical equipment to the UPS output receptacles or power distribution unit, keeping within the rated load.

  6. Set up automatic shutdown

    Connect the USB cable from the UPS to the computer and install the manufacturer's power-management software (or use the operating system's built-in UPS support) so it shuts down gracefully before the battery runs out.

  7. Run a self-test

    Once the battery is charged, start a self-test from the front panel or software to confirm that the UPS transfers to battery correctly.

Using your UPS

How this UPS protects your equipment

As an online double-conversion UPS, it continuously converts incoming AC to DC and back to clean AC, so connected equipment is isolated from voltage and frequency disturbances and there is no transfer time when the utility fails. Because it supports multiple normal modes, it can also run in a high-efficiency (eco) mode that passes filtered utility power through when conditions are good and switches back to double conversion when they are not. Its default operating mode is classified as VFD (voltage and frequency dependent). That means it ships set to its high-efficiency mode; select double-conversion (VFI) mode in the settings if your equipment needs full-time conditioning and zero transfer time.

Battery runtime

According to the certification record, the internal battery provides about 8 minutes at full rated load (15 kW) and about 23 minutes at half load (7,500 W). Runtime is not linear — halving the load usually more than doubles it — and it falls as the battery ages or gets warm. Use the runtime to ride through short outages and to shut systems down cleanly during longer ones.

Monitoring and alerts

The UPS provides USB communication. Configure email or SNMP alerts for on-battery, low-battery, overload and replace-battery events.

Alarms and everyday use

  • An intermittent beep usually means the UPS is running on battery. Save your work; if the outage continues, shut down connected equipment before the low-battery alarm.
  • A continuous tone or overload indicator means the connected load is too high. Unplug non-essential devices from the battery outlets.
  • Leave the UPS switched on and plugged in at all times so the battery stays charged.

Care and maintenance

WhenWhat to do
MonthlyCheck the front-panel status or software for alarms, confirm the load percentage, and make sure vents are clear of dust and obstructions.
Every 6 monthsRun a self-test (or confirm the automatic self-test passed). Where supported, perform a runtime calibration during a maintenance window, as it discharges the battery.
Every 3–5 yearsReplace VRLA batteries. Typical life is 3–5 years at 77 °F (25 °C); roughly every 15 °F (8 °C) above that can cut battery life in half.
AnnuallyCheck for firmware and software updates and confirm that automatic shutdown still works by running a controlled test.

Troubleshooting

Use the front-panel indicators, display messages and event log to narrow down problems. For specific alarm codes, consult the manufacturer's manual or support line.

ProblemPossible causeWhat to try
UPS will not turn onBattery disconnected or deeply discharged; input breaker or fuse open; no utility power.Check the battery connection, verify the outlet or input breaker, and let the UPS charge for several hours before trying again.
Beeps and runs on battery with power presentInput voltage or frequency outside limits; loose input plug; generator power.Check the input connection, try a different circuit, and adjust input sensitivity if the manual permits.
Overload alarmConnected load above the rating; high inrush device on battery outlets.Reduce the load below 15 kW and move printers or heaters off the UPS.
Short runtime or self-test failureAged or hot battery; battery not fully charged.Charge fully and retest; replace the battery if runtime remains well below the rated figures.
Replace-battery indicator onBattery at end of life.Order the specified replacement battery and replace it as described in the manual (or by service for larger units).
Site wiring fault indicatorMissing ground or reversed hot/neutral in the building wiring.Have a qualified electrician inspect the outlet and wiring before connecting equipment.
Computer does not shut down automaticallyCommunication cable not connected; software not installed or not configured.Connect the USB or serial cable (or configure the network card), install the management software, and test with a simulated outage.
Unexpected transfers in eco modeUtility disturbances causing the UPS to leave high-efficiency mode.Review the event log; if transfers are frequent, consider keeping the UPS in double-conversion mode for that site.

Energy use and running costs

A UPS uses energy as conversion and charging losses on top of what your equipment consumes. The Liebert ITA2-15KRT208C has an ENERGY STAR weighted efficiency of 94.5%. The table estimates its losses if it supports a steady load 24 hours a day, 365 days a year, at $0.17 per kWh.

Losses calculated from the efficiency measured at each load point in the minimum tested configuration.
LoadEfficiencyPower lostLosses per yearCost per year
25% (3,750 W)92.9%287 W2,511 kWh$427
50% (7,500 W)94%479 W4,194 kWh$713
75% (11.3 kW)93.9%731 W6,402 kWh$1,088
100% (15 kW)93.4%1,060 W9,285 kWh$1,578

Even with nothing connected, the UPS draws about 151 W to keep its electronics and battery charger running — around 1,326 kWh ($225) a year.

Running in high-efficiency (eco) mode, where appropriate for your site, reduces these losses further. Loading a UPS very lightly lowers its efficiency, so choosing a unit sized reasonably close to your actual load keeps losses down.

Frequently asked questions

How much equipment can the Liebert ITA2-15KRT208C power?

It is rated at 15 kW (15 kVA). Keep the connected load below that — ideally under about 12 kW — to allow for surges and battery aging.

How long will the Liebert ITA2-15KRT208C run on battery?

The certification record lists 8 minutes at full load and 23 minutes at half load. Lighter loads run longer; older or warm batteries run shorter.

What type of UPS is the Liebert ITA2-15KRT208C?

It uses a multi-mode double-conversion topology and defaults to VFD (voltage and frequency dependent) operation. Double conversion gives the highest level of power conditioning with zero transfer time.

How efficient is the Liebert ITA2-15KRT208C?

Its ENERGY STAR weighted efficiency is 94.5%. At half load (7,500 W) it is 94% efficient, losing about 479 W — roughly $713 a year if run continuously at $0.17/kWh.

What battery does the Liebert ITA2-15KRT208C use?

It uses a valve-regulated lead-acid (VRLA) battery (internal). The certification record lists a 1-year battery warranty.

Sources and disclaimer

Specifications on this page come from the ENERGY STAR certified ups battery backups dataset published by the U.S. Environmental Protection Agency (record certified May 6, 2024), retrieved October 7, 2026.

The setup, operating, maintenance and troubleshooting guidance is written by ManualHarbor's editors for this specific product type and configuration. It is an independent guide — not a reproduction of the manufacturer's manual — and ManualHarbor is not affiliated with Liebert. Always follow the safety instructions, installation requirements and warranty terms supplied with your unit, and contact Liebert or an authorized service provider for warranty repairs and replacement parts.

Running-cost figures use assumed U.S. average utility prices and are estimates for comparison only. See our editorial methodology for details.