UPS Battery BackupsOnline Double-Conversion

Mitsubishi SUMMIT SERIES UPS Battery Backup Manual

Setup, everyday use, maintenance and troubleshooting for the 750 kVA / 750 kW online double-conversion UPS, with verified specifications.

  • Rating750 kVA / 750 kW
  • TopologyOnline Double-Conversion
  • Efficiency98%

About the Mitsubishi SUMMIT SERIES

This guide covers the Mitsubishi SUMMIT SERIES, a 750 kVA / 750 kW online double-conversion UPS listed as ENERGY STAR certified.

It can support up to 750 kW of connected equipment (750 kVA apparent power, a 1.00 output power factor). It is rated for 384–552 V, 54–66 Hz input and 466–494 V output, a three-phase service typical of data centers and large commercial buildings. Energy storage is a valve-regulated lead-acid (VRLA) battery (separate battery cabinet).

ENERGY STAR weighted efficiency is 98%, and 98.1% at half load. With nothing connected it draws 3,681 W. Its weighted efficiency is higher than 100% of the 150 Online Double-Conversion models in our database.

The manufacturer lists it for data center applications.

Specifications

Mitsubishi SUMMIT SERIES specifications
BrandMitsubishi
Model numberSUMMIT SERIES
TopologyOnline Double-Conversion
Apparent power rating750,000 VA
Real power rating750,000 W
Output power factor (W/VA)1.00
Default normal modeVFI (voltage and frequency independent)
Intended applicationsData Center
Rated input voltage384–552 V
Rated output voltage466–494 V
Input frequency54–66 Hz
Battery technologyValve-regulated lead-acid (VRLA)
Battery locationSeparate battery cabinet
Weighted efficiency (ENERGY STAR)98.0%
Efficiency at 25% load97.7%
Efficiency at 50% load98.1%
Efficiency at 75% load97.9%
Efficiency at 100% load97.5%
Input power at no load3,681.0 W
Input power factor1.00
Rack-mountableNo
Height80.6 in.
Width81.6 in.
Depth33.8 in.
Modular designNo
Communication portsEthernet, USB
Management protocolsModbus TCP, Modbus RTU
Manufacturer take-back programNo

Safety information

  • Installation, wiring, battery-cabinet connection and start-up must be performed by qualified electricians or manufacturer-authorized field engineers in accordance with NFPA 70 (National Electrical Code) and local codes.
  • Hazardous voltage is present from the battery and from any parallel or bypass sources even when the input breaker is open. Follow lockout/tagout procedures, verify absence of voltage, and wear arc-flash PPE appropriate to the labeled hazard level.
  • Batteries can deliver dangerous energy even when the UPS is disconnected from utility power, and its output terminals may be live on battery power. Only trained service personnel should open cabinets or service battery strings.
  • Install the UPS indoors in a clean, dry, well-ventilated location away from heat sources and direct sunlight. High temperatures shorten battery life sharply.
  • Cabinets of this size must be moved upright with a pallet jack or proper rigging and anchored as the installation manual specifies, including seismic anchoring where local codes require it.

Installation and first-time setup

Base sizing on the critical load. Use the measured or calculated critical load from the electrical design, plus planned growth, and keep normal operation below about 80% of the 750 kW rating. Redundant (N+1) configurations should be sized so the load is still carried with one module out of service.

  1. Plan the site

    Confirm floor loading, service clearances front and rear, cooling capacity and the ambient temperature (about 77 °F / 25 °C is the usual design point for battery life). The cabinet measures about 80.6 × 81.6 × 33.8 in. (H × W × D; 2,047 × 2,073 × 858 mm).

  2. Electrical design

    Have the electrical engineer size the input and bypass feeders, breakers and grounding for 384–552 V three-phase service. A wrap-around maintenance bypass is strongly recommended so the load can stay powered during service.

  3. Install batteries

    Position and interconnect the separate battery cabinets as specified; battery string connections must be made by trained personnel.

  4. Commission

    Have the manufacturer's authorized service perform start-up: verifying wiring and phase rotation, configuring operating modes and alarms, and running load and battery tests.

Using your UPS

How this UPS protects your equipment

As an online double-conversion UPS, it continuously converts incoming AC to DC and back to clean AC, so connected equipment is isolated from voltage and frequency disturbances and there is no transfer time when the utility fails. Its default operating mode is classified as VFI (voltage and frequency independent).

Monitoring and alerts

The UPS provides Ethernet and USB communication. Supported management protocols include Modbus TCP and Modbus RTU, so it can integrate with network-management and building-management systems. Configure email or SNMP alerts for on-battery, low-battery, overload and replace-battery events.

Alarms and everyday use

  • An intermittent beep usually means the UPS is running on battery. Save your work; if the outage continues, shut down connected equipment before the low-battery alarm.
  • A continuous tone or overload indicator means the connected load is too high. Unplug non-essential devices from the battery outlets.
  • Leave the UPS switched on and plugged in at all times so the battery stays charged.

Care and maintenance

WhenWhat to do
MonthlyCheck the front-panel status or software for alarms, confirm the load percentage, and make sure vents are clear of dust and obstructions.
Every 6 monthsRun a self-test (or confirm the automatic self-test passed). Where supported, perform a runtime calibration during a maintenance window, as it discharges the battery.
Every 3–5 yearsReplace VRLA batteries. Typical life is 3–5 years at 77 °F (25 °C); roughly every 15 °F (8 °C) above that can cut battery life in half.
AnnuallySchedule preventive maintenance by authorized service personnel: thermal imaging of connections, capacitor and fan inspection, firmware updates and battery string testing.

Troubleshooting

Use the front-panel indicators, display messages and event log to narrow down problems. For specific alarm codes, consult the manufacturer's manual or support line.

ProblemPossible causeWhat to try
UPS will not turn onBattery disconnected or deeply discharged; input breaker or fuse open; no utility power.Check the battery connection, verify the outlet or input breaker, and let the UPS charge for several hours before trying again.
Beeps and runs on battery with power presentInput voltage or frequency outside limits; loose input plug; generator power.Check the input connection, try a different circuit, and adjust input sensitivity if the manual permits.
Overload alarmConnected load above the rating; high inrush device on battery outlets.Reduce the load below 750 kW and move printers or heaters off the UPS.
Short runtime or self-test failureAged or hot battery; battery not fully charged.Charge fully and retest; replace the battery if runtime remains well below the rated figures.
Replace-battery indicator onBattery at end of life.Order the specified replacement battery and replace it as described in the manual (or by service for larger units).
Site wiring fault indicatorMissing ground or reversed hot/neutral in the building wiring.Have a qualified electrician inspect the outlet and wiring before connecting equipment.
Computer does not shut down automaticallyCommunication cable not connected; software not installed or not configured.Connect the USB or serial cable (or configure the network card), install the management software, and test with a simulated outage.

Energy use and running costs

A UPS uses energy as conversion and charging losses on top of what your equipment consumes. The Mitsubishi SUMMIT SERIES has an ENERGY STAR weighted efficiency of 98%. The table estimates its losses if it supports a steady load 24 hours a day, 365 days a year, at $0.17 per kWh.

Losses calculated from the efficiency measured at each load point in the minimum tested configuration.
LoadEfficiencyPower lostLosses per yearCost per year
25% (188 kW)97.7%4,414 W38,667 kWh$6,573
50% (375 kW)98.1%7,263 W63,624 kWh$10,816
75% (563 kW)97.9%12,066 W105,697 kWh$17,969
100% (750 kW)97.5%19,231 W168,462 kWh$28,638

Even with nothing connected, the UPS draws about 3,681 W to keep its electronics and battery charger running — around 32,245 kWh ($5,482) a year.

Loading a UPS very lightly lowers its efficiency, so choosing a unit sized reasonably close to your actual load keeps losses down.

Frequently asked questions

How much equipment can the Mitsubishi SUMMIT SERIES power?

It is rated at 750 kW (750 kVA). Keep the connected load below that — ideally under about 600 kW — to allow for surges and battery aging.

What type of UPS is the Mitsubishi SUMMIT SERIES?

It uses an online double-conversion topology and defaults to VFI (voltage and frequency independent) operation. Double conversion gives the highest level of power conditioning with zero transfer time.

How efficient is the Mitsubishi SUMMIT SERIES?

Its ENERGY STAR weighted efficiency is 98%. At half load (375 kW) it is 98.1% efficient, losing about 7,263 W — roughly $10,816 a year if run continuously at $0.17/kWh.

What battery does the Mitsubishi SUMMIT SERIES use?

It uses a valve-regulated lead-acid (VRLA) battery (separate battery cabinet).

Can the Mitsubishi SUMMIT SERIES be monitored over the network?

Yes. It has an Ethernet connection and supports Modbus TCP and Modbus RTU.

Sources and disclaimer

Specifications on this page come from the ENERGY STAR certified ups battery backups dataset published by the U.S. Environmental Protection Agency (record certified October 31, 2017), retrieved October 7, 2026.

The setup, operating, maintenance and troubleshooting guidance is written by ManualHarbor's editors for this specific product type and configuration. It is an independent guide — not a reproduction of the manufacturer's manual — and ManualHarbor is not affiliated with Mitsubishi. Always follow the safety instructions, installation requirements and warranty terms supplied with your unit, and contact Mitsubishi or an authorized service provider for warranty repairs and replacement parts.

Running-cost figures use assumed U.S. average utility prices and are estimates for comparison only. See our editorial methodology for details.